Erie Water Treatment Controls
 
 
 

Products
2400 NGC
568
2200
541-400
541-008
541/542-009
541-030
542-030

 

 

 

 

 

 

 

 

 

 

 

2200 Eazy Electronic

Valve Material

Glass-Filled Noryl®

Regeneration Initiation

Time Clock (1-90 Days)
   Demand Time Clock Control (Hardness Setting 1-99 grs.)
   Demand With Day Override (1—7 Days)

Flow Rate @ 40 psi (2.76 bar) Inlet
   Continuous @ 15 psi (1.03 bar) Drop
   Peak @ 25 psi (1.72 bar) Drop
   Backwash @ 40 psi (2.76 bar) Drop

System*
25.0 gpm/94.6 lpm
32.0 gpm/121.1 lpm
12.6 gpm/47.7 lpm

Service

Cv 6.35, Kv 5.5

Backwash

Cv 2.00, Kv 1.7


Regeneration

5 Cycles

Adjustable

1-Minute Increments

Cycles

Backwash (0-20 Minutes)
Brine/Slow Rinse (0-120 Minutes)
Fast Rinse/Brine Tank Fill (0-65 Minutes)
Service


Connections/Dimensions

 

Tank Connection
Inlet/Outlet
Riser Connection
Drain Connection
Brine Line Connection

2 1/2"–8 NPSM
1 5/8"–12UN-2A
1.050"/26.7 mm
3/4" NPT
3/8"/9.5 mm


Ratings

 

Electrical Rating
Operating Pressure
Hydrostatic Test Pressure
Operating Temperature

24V AC (500MA), 50/60 Hz
20 psi–120 psi/1.37 bar–8.28 bar
600 psi/41.4 bar
35°F–120°F/2°C–48°C


Options

 

BWFC Available (gpm)

1.6, 1.8, 2.0, 2.2, 2.6, 3.0, 3.5, 4.0, 5.0, 6.0, 7.0, 8.0, 9.0, 10.0

BLFC Available (gpm)

0.25, 0.50, 1.00

Fitting Kits

3/4" Copper Tube (Sweat)
1" Copper Tube (Sweat)
3/4" NPT Female Brass Adapter
3/4" BSP Female Brass Adapter
1" BSP Male Brass Adapter
3/4" 90° Elbow (Sweat)

Plastic Bypass

Full 1" Ported

Upper Collector

1.050" Riser

 

*Valve mounted on 16" tank with distributor system.